INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
SERIES 3™
Gas - Fired Boiler
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
3 _ _
Boiler Serial Number Installation Date
Heating Contractor Phone Number
Address
9700609
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - SERIES 3™

102998-01R1-7/10INSTALLATION, OPERATING ANDSERVICE INSTRUCTIONS FORSERIES 3™Gas - Fired BoilerFor service or repairs to boiler, call your heating cont

Page 2 - WARNINGS FOR THE INSTALLER

102. Screw the water supply manifold into the boiler outlet tapping “O.”3. Orient the manifold with the relief valve on top.4. Screw the relief val

Page 3 - What's in the crate?

117. Screw an installer-supplied 1¼” pipe or nipple into the water return tapping “R”.8. Screw the supplied drain valve into tapping “D”.6. CONNECT

Page 4 - SPECIFICATIONS

12 DISCONNECT ELECTRICAL POWER to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock ele

Page 5 - SPECIFICATIONS (continued)

13Using IQ Boiler Control Display8. PROGRAM THE CONTROLSViewing the Operating Mode OptionsIn operating mode the user may view (but not change) boiler

Page 6 - BOILER QUICK-START

14Unit DisplayORSample Display1 sec1 sec1 sec Please note that in operating mode to hold the display on the value the user can press and hold either t

Page 7 - 2. POSITION THE BOILER

159. CHECK FOR GAS AND WATER LEAKS GAS LEAKS may result in re or explosion. WATER LEAKS may cause extensive property dam

Page 8 - 3. PROVIDE COMBUSTION AIR

1610-b10. PERFORM STARTUP CHECKS AND ADJUSTMENTS FAILURE TO PERFORM THESE CHECKS of the boiler's combustion and safety systems may

Page 9 - 4. CONNECT VENTING

17ANNUAL MAINTENANCE CHECKLIST WARNINGSTHE BOILER CONTAINS REFRACTORY CERAMIC FIBER, a possible human carcinogen Use a NIOSH approved respirator whe

Page 10 - 5. CONNECT GAS PIPING

18TROUBLESHOOTINGIQ Boiler Control Status Codes (when "Err" is not displayed)Display Status Boiler / Control Action(s)BlankBoiler and Circul

Page 11

19If "Err" IS displayed on the IQ Boiler Control: "Err" ashes on the IQ Boiler control display followed by a number. Use the fo

Page 12 - 7. CONNECT ELECTRICAL WIRING

2FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler.INSPECT THE BOILER ANNUALLY. To keep your boiler safe and efcie

Page 13 - 8. PROGRAM THE CONTROLS

20TROUBLESHOOTING (continued)If IQ Boiler Control Shows Status Code “STA 15": The IQ Boiler Control is “Waiting for Limit to Close” and the dis

Page 14 - Unit Display

21Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3091A Block Assembly 102287-03 102287-04 102287-05 102287-06 102287-07 102287-08 10

Page 15

22REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3092A Base Wrapper 71807031 71807041 71807051 71807061

Page 16

23REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3093AGas Valve (Natural Gas), Honeywell VR8204P1171816

Page 17 - WARNINGS

24REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3094A IQ Boiler Control 102289-014B IQ Option Panel 10

Page 18 - TROUBLESHOOTING

25Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3095A Jacket Left Side Panel 102566-015B Jacket Right Side Panel 102567-015C Jacket

Page 19 - TROUBLESHOOTING (continued)

26REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303 304 305 306 307 308 3096A Supply Water Manifold 806070016B Temperature/Pre

Page 20

27INTERNAL WIRING Figure IW-1: Wiring Diagram

Page 21 - REPAIR PARTS LIST

28INTERNAL WIRING (continued)Figure IW-2: Wiring Schematic

Page 22 - REPAIR PARTS LIST (continued)

29Figure IW-3: Single Zone System with Domestic Hot Water TankFigure IW-4: Multiple Zone System with Zone CirculatorsINTERNAL WIRING (continued)

Page 23

352134Congratulations on your purchase of a new Burnham® boiler—designed and constructed to provide you with years of reliable service. • Cast iron

Page 24

30Figure IW-5: Multiple Zone System with Zone ValvesFigure IW-6: Multiple Zone System with Zone Circulator PanelINTERNAL WIRING (continued)

Page 25

31T STAT 1VALVE 1T STAT 2VALVE 2T STAT 3OFFONZONE 4 PRIORITYTACO ZVC 404 (OR EQIV.)FOUR ZONE ZONE VALVE CONTROLWITH OPTIONAL PRIORITYTHERMOSTATBOILER

Page 26

32APPENDIX A – COMBUSTION AIR PROVIDE ENOUGH AIR to ventilate the boiler room, dilute the ue gases, and sustain combustion. Ignition fail

Page 27 - INTERNAL WIRING

33APPENDIX B – VENTING VENT THIS BOILER according to the instructions. Failure to do so may cause products of combustion to enter the buil

Page 28 - INTERNAL WIRING (continued)

34être prises pour chaque appareil toujours raccordé au système d’evacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés

Page 29

35APPENDIX B1 – ATMOSPHERIC VENTINGFigure B-1: Typical Atmospheric Vent Installation GENERAL WARNINGS FOR ATMOSPHERIC VENTING SYSTEMSUSE ATMOSPHERI

Page 30

36 AVERTISSEMENTS GÉNÉRAUX POUR LES SYSTÈMES D’ÉVACUATION DES PRODUITS DE LA COMBUSTION DU GAZ DANS L’ATMOSPHÈREAPPENDICE B1 – SYSTÈMES D’ÉVAC

Page 31

37APPENDIX C – GAS PIPING ASSURE GAS PIPING IS LEAK FREE AND OF PROPER SIZE and type for the connected load. SHUT OFF MAIN GAS SUPPLY

Page 32 - APPENDIX A – COMBUSTION AIR

385. Bond all above-ground gas piping to a grounding electrode and ensure the piping is electrically continuous. DO NOT USE GAS PIPING AS A

Page 33 - APPENDIX B – VENTING

39(2) Comply with the boiler’s specic water quality requirements. See the Specifications Section of this manual.(3) Comply with the boiler’s

Page 34

4Series 3Boiler ModelInput (MBH) DOE Heating Capacity (MBH) Net I=B=R Rating (MBH) AFUE (%)303 70 59 51 84304 105 88 77 84305 140 117 102 84306 175 14

Page 35

40Figure D-0: Piping Schematic SymbolsAPPENDIX D – System Piping (continued)

Page 36

41Figure D-W1: Water Boiler, Series LoopAPPENDIX D – System Piping (continued)Figure D-W2: Water Boiler, Two or More Zones

Page 37 - APPENDIX C – GAS PIPING

42Figure D-W3: Water Boiler, Tankless Coil, Two or More ZonesAPPENDIX D – System Piping (continued)Figure D-W4: Water Boiler, Indirect Water Heater,

Page 38 - APPENDIX D – SYSTEM PIPING

43APPENDIX D – System Piping (continued)Figure D-W5: Water Boiler, Indirect Water HeaterFigure D-W6: Multiple Water Boilers, Indirect Water Heater,

Page 39

44APPENDIX E – FILLING THE SYSTEM AND CHECKING FOR LEAKSFill entire heating system with water and vent air from system. Use the following procedure o

Page 40

45APPENDIX F – ADJUSTING GAS INPUT RATENatural Gas Boilers:1. Turn off gas supply to all appliances other than gas-red boiler.2. Note the rated man

Page 41

46Seconds for Two (2) RevolutionsSize of Gas Meter DialOne-Half Cu. Ft.OneCu. Ft.TwoCu. Ft.24 150.0 300.0 450.026 138.4 276.9 415.328 128.5 257.1 385.

Page 42

47APPENDIX G – CHECKING DRAFT AND COMBUSTIONCHECK DRAFT (GAS BOILERS WITH DRAFT HOODS)1. Insofar as is practical, close all doors and windows in the

Page 43

48The IQ Boiler Control stores two boiler supply temperature setpoints in its memory; one setpoint is for the High Limit Setting and the second is for

Page 44

49APPENDIX H – IQ Control System (continued)IQ Option Cards: For example, if additional safety limits are required, select Manual or Automatic Reset A

Page 45

5Figure S-1: Minimum Clearances to Combustibles and Closet DimensionsSPECIFICATIONS (continued)

Page 46

50The LCD Display kit includes a mounting bracket and wiring harness to allow simple physical installation and “plug-in” style electrical connection.

Page 47

51APPENDIX H – IQ Control System (continued)Burnham Part NumberItem Description102723-01Outside Reset IQ Option Card, Domestic Hot Water Priority, for

Page 48

52Subject to the terms and conditions set forth below, U.S. Boiler Company, Inc. Lancaster, Pennsylvania hereby extends the following limited warranti

Page 49

6Installation: 1. Unpack the crate ... 7 2. Position t

Page 50

7 THE BOILER IS TOP-HEAVY. Do not allow it to tip over.1. Remove the sleeve. 2. Remove the contents from the skid, except the boiler.

Page 51 - Additional Information List

83. PROVIDE COMBUSTION AIR INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and release of deadly carbon monoxide (CO) i

Page 52

94-a4. CONNECT VENTING IMPROPER VENTING may result in property damage and the release of ue gases which contain deadly c